Safety Considerations
Gas furnace troubleshooting requires extra caution due to combustion hazards. Always follow these safety protocols:
- Turn off gas supply before working on gas valve or burners
- Use combustible gas detector to check for leaks
- Never bypass safety controls for testing
- Ensure proper ventilation before testing combustion
- Have CO detector present during operation tests
Furnace Sequence of Operation
Understanding the normal sequence helps pinpoint failures:
- Thermostat calls for heat: Sends 24V signal to furnace
- Inducer motor starts: Creates draft for combustion gases
- Pressure switch closes: Confirms proper draft
- Ignitor heats up: Hot surface ignitor glows (60-90 seconds)
- Gas valve opens: Gas flows to burners
- Flame established: Flame sensor confirms combustion
- Blower motor starts: After heat exchanger warms up (30-60 seconds)
- Heating cycle continues: Until thermostat is satisfied
Common No-Heat Problems
1. Dirty Flame Sensor
The #1 cause of "furnace lights then shuts off" complaints. The flame sensor is a simple rod that detects flame by measuring microamps of current. When dirty:
- Burners light normally
- Flame goes out after 3-10 seconds
- Furnace tries again (usually 3 attempts)
- Then locks out on safety
Solution: Clean with fine steel wool or emery cloth. Replace if pitted or cracked.
2. Failed Ignitor
Hot surface ignitors (HSI) have limited lifespan (3-7 years typically). Signs of failure:
- Inducer runs but no ignition attempt
- Ignitor doesn't glow at all
- Ignitor glows weakly (orange instead of bright white)
- Visible cracks in ceramic
3. Pressure Switch Issues
The pressure switch ensures proper draft before allowing ignition. Problems include:
- Blocked condensate drain (high-efficiency furnaces)
- Blocked vent pipe
- Failed inducer motor
- Cracked pressure switch hose
- Bad pressure switch
4. Limit Switch Tripped
The high limit switch shuts off gas if the heat exchanger overheats. Common causes:
- Dirty air filter restricting airflow
- Blocked return air
- Failed blower motor or capacitor
- Closed supply registers
Ignition System Diagnosis
Testing Hot Surface Ignitors
- Remove ignitor from furnace
- Check resistance: should be 40-200 ohms typically
- Infinite resistance = open (failed)
- Very low resistance = shorted (failed)
- Visual check for cracks - even hairline cracks cause failure
Testing Flame Sensors
- Connect microamp meter in series with flame sensor wire
- Start furnace and observe reading
- Good sensor: 2-6 microamps DC
- Weak/dirty: less than 2 microamps
- No reading: bad sensor or ground issue
Gas Valve Testing
Before condemning a gas valve, verify:
- 24V present at valve when calling for heat
- Gas supply is on and pressure is adequate
- All safety interlocks are closed
- Proper ground for flame sensing
Furnace Parts In Stock
NOLT stocks ignitors, flame sensors, gas valves, and more. Same-day delivery for DMV contractors.
Shop Furnace Parts