Initial Assessment
When a customer reports their AC isn't cooling, a systematic approach saves time and ensures you don't miss anything. Start with these initial questions:
- When did the problem start?
- Did anything change recently (power outage, storm, work on the house)?
- Is it blowing air at all, or no air?
- Is the outdoor unit running?
- Are any unusual sounds or smells present?
Quick Visual Check
Before grabbing your tools, do a quick walk-around:
- Check thermostat settings (mode, temperature, fan setting)
- Look at the air filter
- Check that supply and return vents are open
- Observe the outdoor unit (running, frozen, damaged?)
- Look for obvious issues (tripped breaker, disconnected wires)
Thermostat & Controls
Thermostat Issues
The thermostat is often overlooked but causes many "not cooling" complaints:
- Wrong mode: Set to heat, fan only, or off instead of cool
- Set point too high: Set above current room temperature
- Dead batteries: Many thermostats need battery replacement
- Poor location: Near heat source giving false readings
- Loose wiring: Check connections at thermostat and air handler
Testing the Thermostat
- Set thermostat to cool, 5°F below room temperature
- Listen for click indicating call for cooling
- Verify 24V between R and Y terminals at air handler
- If no 24V, check transformer and wiring
Airflow Problems
Restricted airflow is a leading cause of poor cooling and frozen coils.
Common Airflow Restrictions
Dirty Air Filter
The #1 cause of service calls. A clogged filter:
- Reduces airflow across the evaporator
- Causes the coil to freeze
- Makes the system work harder
- Can trip the high-pressure switch
Dirty Evaporator Coil
Even with regular filter changes, coils get dirty over time. Signs include:
- Reduced airflow despite clean filter
- Higher than normal superheat
- Visible dirt on coil surface
- Musty odors from the vents
Blower Motor Issues
- Faulty capacitor (motor hums but won't start)
- Bad motor (no operation at all)
- Wrong speed setting (multi-speed motors)
- Dirty blower wheel (reduced CFM)
Ductwork Problems
- Disconnected ducts in attic or crawlspace
- Crushed flexible duct
- Closed or blocked registers
- Leaky duct connections
Electrical Diagnosis
Power Supply Issues
- Check disconnect at outdoor unit (fuses or breaker)
- Verify 240V at contactor line side
- Check indoor breaker and switch
- Measure 24V at transformer secondary
Component Testing
Capacitor
Test as described in our capacitor troubleshooting guide. A weak or failed capacitor prevents motor startup.
Contactor
Check for pitted contacts, stuck armature, or coil failure. See our contactor guide for details.
Safety Controls
- High-pressure switch: Trips on high head pressure (dirty condenser, overcharge, restriction)
- Low-pressure switch: Trips on low suction pressure (low charge, restriction, low airflow)
- Compressor overload: Internal thermal protection
Refrigerant System
Signs of Low Refrigerant
- Warm air from supply vents
- Ice forming on refrigerant lines or evaporator
- Long run times without reaching set point
- Bubbles in sight glass (if equipped)
- Low suction pressure, low superheat
Checking the Charge
- Connect gauges to service ports
- Measure suction and discharge pressures
- Calculate superheat and subcooling
- Compare to manufacturer specifications
Finding Leaks
If refrigerant is low, always find and fix the leak before recharging:
- Electronic leak detector
- UV dye and blacklight
- Soap bubbles at suspected locations
- Common leak points: service valves, flare connections, evaporator coil, condenser coil
Compressor Issues
Compressor Not Running
If the condenser fan runs but the compressor doesn't:
- Check for 240V at compressor terminals
- Verify capacitor is good
- Check compressor winding resistance (C-R, C-S, R-S)
- Test for grounded windings (megohmmeter to ground)
- Check for locked rotor (amp draw at startup)
Compressor Winding Resistance
For single-phase compressors:
- Measure resistance between all three terminals
- Lowest reading = R (run) to S (start)
- Highest reading = C (common) to opposite terminal
- R-S should equal C-R + C-S
- Infinite reading = open winding (failed)
- Zero/very low = shorted winding (failed)
Common Compressor Problems
- Mechanical failure: Internal damage, locked rotor
- Electrical failure: Burned windings, grounded
- Thermal overload: Temporary shutdown from overheating
- Refrigerant flooding: Liquid refrigerant washing out oil
Get the Parts You Need Fast
NOLT delivers capacitors, contactors, and hard-to-find parts same-day in the DMV area. Pro contractor discounts available.
Shop HVAC PartsDiagnosis Flowchart Summary
- Thermostat calling? → Check settings, wiring, batteries
- Indoor fan running? → Check blower motor, capacitor, control board
- Outdoor unit running? → Check power, contactor, capacitor
- Good airflow? → Check filter, coil, ductwork
- Proper pressures? → Check refrigerant charge, restrictions
- Compressor operating? → Check windings, overload, mechanical